XMLR040G0T26

Electronic pressure sensors, Pressure sensors XM, XMLR 40 bar, 1/4" 18 NPT, 24 VDC, 4...20 mA, M12

End of commercialisation Fecha de fin de comercialización : Fecha de fin del servicio :

Expandir todo

Ficha de datos

Range of product
Telemecanique Pressure sensors XM
Product or component type
Electronic pressure sensors
Pressure sensor type
Pressure transmitter
Pressure switch type of operation
Pressure transmitter
Device short name
XMLR
Controlled fluid
Fresh water (0-80 °C), air (-20-80 °C), hydraulic oil (-20-80 °C), refrigeration fluid (-20-80 °C)
Fluid connection type
1/4" - 18 NPT (female)
[Us] rated supply voltage
24 V DC SELV (voltage limits: 17-33 V)
Current consumption
<= 50 mA
Electrical connection
Male connector M12, 4 pins
Analogue output function
4...20 mA
Type of output signal
Analogue
Analogue output function
4...20 mA
Scale type
Fixed differential
Materials in contact with fluid
316L stainless steel
ceramic
fluorocarbon FKM (Viton)
Front material
Polyester
Housing material
316L stainless steel
polyacrylamide
Operating position
Any position, but disposals can falsified the measurement in case of upside down mounting
Protection type
Overload protection
overvoltage protection
reverse polarity
short-circuit protection
Response time on output
<= 10 ms for analog output
Display type
4 digits 7 segments
Display response time type
Fast 50 ms, normal 200 ms, slow 600 ms
Delay first up
300 MILLISECOND
Accuracy
<= 1 % of the measuring range
Linearity error
<= 0.5 % of the measuring range
Hysteresis
<= 0.2 % of the measuring range
Measurement accuracy
<= 0.6 % of the measuring range
Repeat accuracy
<= 0.2 % of the measuring range
Drift of the sensitivity
+/- 0,03 % of measuring range/°C
Drift of the zero point
+/- 0,01 % of measuring range/°C
Display accuracy
<= 1 % of the measuring range
Electromagnetic compatibility
Susceptibility to electromagnetic fields: 10 V/m 80...2000 MHz conforming to IEC 61000-4-3, immunity to conducted RF disturbances: 10 V 0.15...80 MHz conforming to IEC 61000-4-6, surge immunity test: 1 kV conforming to IEC 61000-4-5, electrical fast transient/burst immunity test: 2 kV conforming to IEC 61000-4-4, electrostatic discharge immunity test: 8 kV air, 4 kV contact conforming to IEC 61000-4-2
Marking
CE
Product certifications
cULus
Standards
IEC 61326-2-3
UL 61010-1
IP degree of protection
IP65 conforming to IEC 60529, IP67 conforming to IEC 60529
Vibration resistance
20 gn (f= 10-2000 Hz) conforming to IEC 60068-2-6
Shock resistance
50 gn conforming to IEC 60068-2-27
Unit type of package 1
PCE
Number of units in package 1
1
California proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Expandir todo

Dibujos tecnicos

Dimensions

epds
  • (1) Fluid entry: 1/4”-18NPT female

Connections and Schema

Connector Wiring

epds
  • (1) I Out or V Out
  • (2) Test Input

Analogue Output Description

epds
  • X : Pressure
  • Y : Analogue output signal
  • (1) An offset of +/-5% of nominal pressure can be compensated (with Configuration menu. : Offset Compensation)
  • (2) The analogue curve can be adjusted from -25% to +25% of nominal pressure (with Configuration menu. : analogue end point).

Back to top

arrow