Mechanical durability
10000000 cycles
Minimum force for tripping
7 N
Maximum actuation speed
10 cm/s
Contact code designation
B300, AC-15 (Ue = 240 V), Ie = 1.5 A conforming to IEC 60947-5-1 appendix A, R300, DC-13 (Ue = 250 V), Ie = 0.1 A conforming to IEC 60947-5-1 appendix A
Electrical durability
5000000 cycles, DC-13, 120 V, 1 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C, 5000000 cycles, DC-13, 24 V, 3 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C, 5000000 cycles, DC-13, 48 V, 2 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Electrical connection
Removable cable connector
Cable composition
5 x 0.75 mm²
Wire insulation material
PvR
Positive opening minimum force
35 N
Contacts insulation form
Zb
Contacts type and composition
1 NC + 1 NO
Contact operation
Snap action
[Uimp] rated impulse withstand voltage
4 kV conforming to IEC 60664, 4 kV conforming to IEC 60947-1
[Ui] rated insulation voltage
300 V (pollution degree 3) conforming to UL 508, 400 V (pollution degree 3) conforming to IEC 60947-5-1, 300 V (pollution degree 3) conforming to CSA C22.2 No 14
Overvoltage category
Class I conforming to IEC 61140, class I conforming to NF C 20-030
Resistance across terminals
25 mOhm conforming to IEC 60255-7 category 3
Short-circuit protection
6 A cartridge fuse, type gG