Cable outer diameter
7…10 mm
Positive opening
With NC contact
Mechanical durability
1000000 cycles
Minimum torque for tripping
0.1 N.m
Positive opening minimum torque
0.25 N.m
Contact code designation
A300, AC-15 (Ue = 120 V, Ie = 6 A) conforming to EN/IEC 60947-5-1
A300, AC-15 (Ue = 240 V, Ie = 3 A) conforming to EN/IEC 60947-5-1
Q300, DC-13 (Ue = 125 V, Ie = 0.55 A) conforming to EN/IEC 60947-5-1
Q300, DC-13 (Ue = 250 V, Ie = 0.27 A) conforming to EN/IEC 60947-5-1
[Ithe] conventional enclosed thermal current
10 A
[Ui] rated insulation voltage
300 V conforming to UL 508
300 V conforming to CSA C22.2 No 14
500 V (pollution degree 3) conforming to EN/IEC 60947-1
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-5-1
Maximum resistance across terminals
30 mOhm conforming to EN/IEC 60947-5-4
Short-circuit protection
10 A cartridge fuse type gG (gl)
Safety level
Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to IEC 61508
Safety reliability data
B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear
Enclosure material
Polyamide PA66 fibre glass impregnated
Lever material
Stainless steel