Minimum actuation speed
6 m/s
Cable entry
2 entries tapped for Pg 11 cable gland, cable outer diameter: 4-8 mm
Contact code designation
B300, AC-15 (Ue = 240 V), Ie = 1.5 A conforming to IEC 60947-5-1 appendix A, R300, DC-13 (Ue = 250 V), Ie = 0.1 A conforming to IEC 60947-5-1 appendix A
Electrical durability
5000000 cycles, DC-13 120 V, 7 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C, 5000000 cycles, DC-13 24 V, 13 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C, 5000000 cycles, DC-13 48 V, 9 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Electrical connection
Screw-clamp terminals, clamping capacity: 1 x 0.5...2 x 2.5 mm²
Positive opening
With, conforming to IEC 60947-5-1 Annex K
Contacts insulation form
Zb
Contacts type and composition
2 NC
Contacts material
Silver plated contacts
Terminals description ISO n°1
(11-12)NC
(21-22)NC
Contact operation
Slow-break, simultaneous
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60664, 6 kV conforming to IEC 60947-1
[Ui] rated insulation voltage
300 V conforming to UL 508, 500 V (pollution degree 3) conforming to IEC 60947-1, 300 V conforming to CSA C22.2 No 14
Short-circuit protection
10 A cartridge fuse, type gG