Electrical connection
Screw-clamp terminals, clamping capacity: 1 x 0.34...2 x 0.75 mm²
Minimum actuation speed
0.01 m/min
[Ie] rated operational current
1.5 A at 240 V, AC-15, B300 conforming to EN/IEC 60947-5-1 appendix A
0.1 A at 250 V, DC-13, R300 conforming to EN/IEC 60947-5-1 appendix A
[Ithe] conventional enclosed thermal current
6 A
[Ui] rated insulation voltage
400 V (pollution degree 3) conforming to IEC 60947-1 for contact block
300 V conforming to CSA C22.2 No 14 for contact block
300 V conforming to UL 508 for contact block
Maximum resistance across terminals
0.25 mOhm conforming to IEC 60255-7 category 3
[Uimp] rated impulse withstand voltage
4 kV conforming to IEC 60664
4 kV conforming to IEC 60947-1
Short-circuit protection
6 A cartridge fuse, type gG
Electrical durability
5000000 cycles, DC-13 120 V, 1 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 24 V, 3 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 48 V, 2 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Terminals description ISO n°1
(31-32)NC
(13-14)NO
(21-22)NC